When
we are field testing a Reduced Pressure Principle Backflow Prevention
Assembly (RP), we are making a diagnostic analysis at one point
in space and time. From this data, we cannot say how the assembly
worked yesterday or if it will work tomorrow, only what it is
doing right now. When we perform the field test we are generating
data on the working of the assembly which we must compare to the
minimum acceptable performance data as established in our accepted
test procedure. Two (2.0) PSID is the minimum acceptable relief
valve opening point, but few assemblies are designed to open at
2.0 PSID. For this reason when we get a performance value from
a field test whether it be a relief valve opening point or a check
valve value, we must understand what is happening in the assembly.
To
understand what happens inside an RP, let us flow water through
a generic RP (see illustration). An RP consists of an inlet and
outlet shut-off valves, four properly located test cocks, a first
and second check valve component and a relief valve component.
Let us hook up our RP to a water source which produces 100PSI
and begin to pressurize the assembly.
As
the inlet shut-off is opened, water enters the inlet of the assembly
ahead of the 1st check valve. Once in this area the water enters
a relief valve sensing line. Some sensing lines are external hose
or pipe and some utilize an internal passageway. The water travels
through this sensing line to the elastic element in the relief
valve. The elastic element is either a diaphragm or a rolling
diaphragm. This pressure will build up on the elastic element
which will deflect and cause the relief valve stem to compress
the relief valve spring and move the relief valve disc to seal
against the relief valve seat. The function of the relief valve
spring is to constantly try to open the relief valve. If the pressure
after the 1st check rises to where it is a minimum of 2.0 PSI
less than the inlet pressure ahead of the 1st check then the 2.0
PSI loading from the relief valve spring would cause the relief
valve to open. In a properly working relief valve, the opening
point can be anywhere from 2.0 – 4.0 PSID depending on the
manufacturer, model and size. Once the water pressure has closed
the relief valve, then the pressure will increase to the next
point which will cause the first check to open and allow the water
to travel past the first check. The water pressure will be reduced
by the amount of pressure it takes to open the first check. The
1st check of an RP can have a loading of anywhere between 5-15
PSI depending on the make, model and size. In our illustration
we will assume our relief valve spring generates a 2.0 PSID and
the first check spring has a 10.0 PSI Loading. Once the 1st check
opens, water will travel past and pressurize the area between
the 1st and 2nd checks. When this area is pressurized it will
also pressurize the low pressure side of our relief valve. The
higher inlet pressure (100 PSI) is placed on the high pressure
side of the elastic element and the lower pressure past the 1st
check (90 PSI) is placed against the low pressure side of the
elastic element. Once this area between the two checks and the
low pressure side of the relief valve is pressurized, the pressure
will now cause the 2nd check to open. The loading of the 2nd check
spring will be anywhere between 1-5 PSI depending on the make
model and size. The pressure after the 2nd check will be reduced
by the amount of pressure it takes to open the 2nd check. For
our illustration, we will give the 2nd check a 5.0 PSI loading.
The
inlet pressure (100PSI) of the RP in our illustration is reduced
by the combined pressure load of the 1st and 2nd check spring
(100 – 10 – 5 = 85 PSI) producing our downside pressure
of 85 PSI. The relief valve spring is continually trying to open
the relief valve which the inlet pressure is keeping closed. A
properly working relief valve can only open when the pressure
after the 1st check plus the relief valve opening point is greater
than the inlet pressure of our RP. In our illustration the pressure
past the 1st check (90 PSI) must increase to 98.1 PSI so that
the value of the relief valve opening point (2.0 PSID) and the
pressure after the 1st check (90 PSI) is now greater (98.1 + 2.0
? 100 PSI) than the inlet pressure.
A
properly working RP will have the relief valve pressured closed
and the check valves will modulate between an opened and closed
position to fill the water demand of the plumbing system. The
two conditions that can cause an RP to not work in a normal condition
are backpressure and backsiphonage. In the next article we will
see what happens inside the RP when backpressure and backsiphonage
are present.
|